-40%
Rib in Box. RIBMN24Q4C Track Mount Style. 4 Output I/O Expander - c
$ 13.19
- Description
- Size Guide
Description
Rib in Box. RIBMN24Q4C Track Mount Style. 4 Output I/O Expander. Condition is "NOT USED". Shipped with USPS Priority Mail.RIB
Track Mount, 4 Output, Field Relay Module
GRAINGER Item #
244W96
Mfr. Model #
RIBMN24Q4C-PX
JOHNSON CONTROLS
Ribmn24Q4Cpx, Ribmn24Q4Cpx
GRAINGER Item #
42A370
Mfr. Model #
RIBMN24Q4C-PX
# Relays & Contact Type: Expected Relay Life: Operating Temperature: Humidity Range: Power Status: Relay Status: Heartbeat Status: Dimensions: Track Mount: Approvals: Gold Flash: Override Switch:
Four (4) SPDT Continuous Duty Coil
10 million cycles minimum mechanical
-30 to 140° F 5 to 95% (noncondensing)
Green LED On = Power On
Red LED On = Relay Activated
Right-most decimal point 4.950˝ x 2.750˝ x 1.750˝
MT212-6 Mounting Track Provided UL Listed, UL916, C-UL, CE,
RoHS No No RIBMN24Q4C-PX 2.75˝ Track Mount 4 Output
Field Adjustable Staging Threshold
Relay Module with 24 Vac/dc Power and 0-10 Vdc Control Input Contact Ratings:
15 Amp General Use @ 125 Vac
10 Amp General Use @ 277 Vac
10 Amp Resistive @ 30 Vdc (N/O)
7 Amp Resistive @ 30 Vdc (N/C)
1/2 HP @ 125 Vac
1 HP @ 250 Vac
1/4 HP @ 277 Vac 470 VA
Pilot Duty @ 125 Vac 770 VA
Pilot Duty @ 250 Vac Power
Input: 24 Vac/dc ; 50-60 Hz 200mA max.
Notes: •
For AC applications, an isolation transformer, to be used solely for the power input, is recommended. •
Relay will activate when control signal voltage reaches or exceeds individual relay ON point.
Relay will deactivate when control voltage reaches or drops below individual OFF point. •
Factory relay ON / OFF voltages: •
Relay 1: 3V / 2.8V •
Relay 2: 5V / 4.8V •
R
elay 3: 7V / 6.8V •
Relay 4: 9V / 8.8 V •
Minimum ON point: 0.5V •
Maximum ON point: 9.9V •
Minimum OFF point: 0.3V •
Relay number will flash 3 times when voltage exceeds setpoint. •
Pressing UP or DN button in normal run mode will display the voltage present on Analog Input. •
ON/OFF points can be changed at any time, by the user, by entering “Program Mode” •
User defined ON/OFF points will be maintained upon power loss.